Data Center Spatio-Temporal Load Flexibility in Security-Constrained Unit Commitment for Enhanced Grid Efficiency and Reliability
Haoxiang Wan, Xingpeng Li
- Year
- 2026
- Access
- Open access
Abstract
Data center electricity consumption reached 4.4% of U.S. total in 2023 and is projected to grow to 6.7--12% by 2028, imposing increasing stress on transmission networks while representing a largely untapped source of controllable demand-side flexibility. This paper proposes a modular security-constrained unit commitment (SCUC) framework that coordinates flexible data center workloads with system-level scheduling to reduce renewable curtailment, alleviate congestion, and lower operating costs. Three mixed-integer linear programming (MILP) models are formulated: the Data Center Spatial model (DC-S), enabling instantaneous workload redistribution across geographically distributed sites; the Data Center Temporal model (DC-T), permitting each site to shift its deferrable load across time while preserving the daily energy balance; and the Data Center Spatio-Temporal model (DC-ST), jointly activating both mechanisms and spanning the largest feasible operating region. Case studies on a modified IEEE 24-bus reliability test system show that DC-ST eliminates all base-case and post-contingency transmission violations at a flexibility ratio of 40%, and reduces renewable curtailment by up to 84.4% at 30% relative to the inflexible baseline. Sensitivity analysis further reveals that moderate flexibility levels of 20%--30% already capture most of the achievable benefits, supporting practical deployment with limited operational burden on data center operators.
Keywords
Related papers
Statistical Learning Theory
Yuhai Wu, Vladimir Vapnik
1999
Fractional Differential Equations
Igor Podlubný
2025
Applied Nonlinear Control
Jean-Jacques Slotine, Weiping Li
1991
Genetic Programming: On the Programming of Computers by Means of Natural Selection
John R. Koza
1992