Real-time Load Current Monitoring of Overhead Lines Using GMR Sensors
Md Mahfuzur Rahman Chy, Md Rifat Al Amin Khan, Md Sultan Mahamud, Anwarul Islam Sifat, Fiona J. Stevens McFadden
- 发表年份
- 2026
- 访问权限
- 开放获取
摘要
Non-contact current monitoring has emerged as a prominent research focus owing to its non-intrusive characteristics and low maintenance requirements. However, while they offer high sensitivity, contactless sensors necessitate sophisticated design methodologies and thorough experimental validation. In this study, a Giant Magneto-Resistance (GMR) sensor is employed to monitor the instantaneous currents of a three-phase 400-volt overhead line, and its performance is evaluated against that of a conventional contact-based Hall effect sensor. A mathematical framework is developed to calculate current from the measured magnetic field signals. Furthermore, a MATLAB-based dashboard is implemented to enable real-time visualization of current measurements from both sensors under linear and non-linear load conditions. The GMR current sensor achieved a relative accuracy of 64.64% to 91.49%, with most phases above 80%. Identified improvements over this are possible, indicating that the sensing method has potential as a basis for calculating phase currents.